Permit: T04CM01510

Parcel: 141174290

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/24/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*/ 1) NOTE; #3 SHEAR REQUIRED AT GARAGE TO HOUSE WALL, HOUSE SIDE
05/11/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ITEM #5 OF 5/7/04 NOT COMPLIED WITH
05/07/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) ROOF NAIL OK 2) END TRUSS EAST 3 PT BEARING (SHIM) 3) 36" STRUT STRAPS AT 3 PTS GARAGE OPENING 4) FILL IN 1" STRIP ROOF DECK ABOVE REAR BAY WINDOW 5) #3 SHEAR WALL AT DINNING ROOM WEST WALL 3 CAR OPT, YOU INSTALLED A WINDOW NOT ON PLAN. ADD THAT MUCH MORE SHEAR TO TOTAL LENGTH OF SHEAR WALL