Permit: T04CM01502

Parcel: 13510150R

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/09/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR FINAL C OF O. LEFT GAS CARD.
04/08/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) EXHAUST FAN OVERFUSED AT 30 AMP. MARK DATA PLATE ON FAN WHICH MOTOR IS INSTALLED, WHAT VOLTAGE. FUSE ACCORDINGLY. SECURE ELEC. SEAL TITE. PUT BLACK TAPE ON WHITE WIRE. RE-CALL FOR INSP. OK FOR C OF O.