Permit: T04CM01502

Parcel: 13510150R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/09/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*CORRECTION MADE - TWO BACKFLOW IN HOUSE CERTIFICATIONS. GAS CARD BY MECH.
04/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 14 PSI AIR TEST FROM METER TO RANGE, 2 STACKED OVENS AND WTR HTR PARTIAL APPROVAL. 1) INSTALL GAS COCKS PER PLAN AT STACKED OVENS - 1 VALVE PER APPLIANCE. 2) RIDGID PIPE WTR HTR T&P DRAIN PIPING. 3) PLEASE HAVE ALL BACKFLOW CERTIFICATIONS ON SITE.