Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ OK ROUGH. | |
| 06/08/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WE STILL HAVE BOX OVER FILL IN KITCHEN. 18.0 CU. BOX CANNOT HAVE 3 #12'S. 2 GANG BY ARCH. OVERFILLED. #12 = 2.5 C.U. DEVICES = 2. ALL GROUNDS TOGETHER = 2.5 A REFEE MAY BE NECESSARY IF NOT COMPLETED NEXT INSP. | |
| 06/01/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ FINISH 2,3, AND 5 FROM PREVIOUS INSP. | |
| 05/24/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) FINISH BOXES MAKE-UP. 2) STAPLE NM CABLE WITHIN 12" OF BOX. 3) INSERT NM CABLE INTO BOX ΒΌ" OR MORE OF SHEATHING. 4) SUPPORT ALL CABLES AND CONDUIT ABOVE PANEL. 5) WE HAVE CONDUCTOR OVERFILL AT BOX. 6) PROTECT CABLES AT STUDS. 7) BOND JUNCTION BOX ENCLOSURE. 8) WHY ARE WE SPLICING #14 WIRE TO #12 WIRE? 9) PROVIDE WTR AND GAS BOND. 10) SINGLE GANG BOX NOT ALLOWED FOR LIGHT FIXTURE. | |
| 05/20/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920*/ DOOR LOCKED NO ACCESS. |