Permit: T04CM01496

Parcel: 11108009A


Addresses:

3610 E GLENN ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/10/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ OK ROUGH.
06/08/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) WE STILL HAVE BOX OVER FILL IN KITCHEN. 18.0 CU. BOX CANNOT HAVE 3 #12'S. 2 GANG BY ARCH. OVERFILLED. #12 = 2.5 C.U. DEVICES = 2. ALL GROUNDS TOGETHER = 2.5 A REFEE MAY BE NECESSARY IF NOT COMPLETED NEXT INSP.
06/01/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ FINISH 2,3, AND 5 FROM PREVIOUS INSP.
05/24/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) FINISH BOXES MAKE-UP. 2) STAPLE NM CABLE WITHIN 12" OF BOX. 3) INSERT NM CABLE INTO BOX ΒΌ" OR MORE OF SHEATHING. 4) SUPPORT ALL CABLES AND CONDUIT ABOVE PANEL. 5) WE HAVE CONDUCTOR OVERFILL AT BOX. 6) PROTECT CABLES AT STUDS. 7) BOND JUNCTION BOX ENCLOSURE. 8) WHY ARE WE SPLICING #14 WIRE TO #12 WIRE? 9) PROVIDE WTR AND GAS BOND. 10) SINGLE GANG BOX NOT ALLOWED FOR LIGHT FIXTURE.
05/20/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*/ DOOR LOCKED NO ACCESS.