Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM01478

Parcel: 128100800

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM01478

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ OK FOR C OF O.
05/25/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LABEL OR IDENTIFY VAV BOXES. CLIMATIC WILL PROVIDE LABELING. 2) 20 AMP FUSES TOO LARGE FOR VAV BOXES. 15 AMP IS MAX. FINISH CONNECTING POWER TO VAV BOXES. 3) FRAME TRANSFER OPENINGS IN WALL TO PROPER SIZE. RECALL FOR INSPECTION.