Permit: T04CM01475

Parcel: 12701005D

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM01475

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
06/29/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BONDING DEVICE AT CONCENTRICS ARE NEEDED PER 250-97. 2) CANNOT STACK LUGS. 3) LABEL DISCONNECT AND STARTER. 4) PLEASE VERIFY 600 VOLT RATING FOR CONTROL WIRING. 5) USE APPROVED FITTINGS - CHASE NIPPLE NOT APPROVED WITH COUPLING. 6) FILL UNUSED OPENING IN DISCONNECT. 7) WHERE IS ONE LINE DIAGRAPH FOR WIRING OF STARTER AND COIL POWER. 8) USE PROPER APPROVED METHODS TO CONNECTING TO INCOMING BUSS. 9) PLEASE HAVE SOMEONE AVAILABLE TO ACCESS EQUIPMENT FOR INSP. 10) SUPPORT CONTROL WIRE CONDUIT AS PER CODE.