Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM01475
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) BONDING DEVICE AT CONCENTRICS ARE NEEDED PER 250-97. 2) CANNOT STACK LUGS. 3) LABEL DISCONNECT AND STARTER. 4) PLEASE VERIFY 600 VOLT RATING FOR CONTROL WIRING. 5) USE APPROVED FITTINGS - CHASE NIPPLE NOT APPROVED WITH COUPLING. 6) FILL UNUSED OPENING IN DISCONNECT. 7) WHERE IS ONE LINE DIAGRAPH FOR WIRING OF STARTER AND COIL POWER. 8) USE PROPER APPROVED METHODS TO CONNECTING TO INCOMING BUSS. 9) PLEASE HAVE SOMEONE AVAILABLE TO ACCESS EQUIPMENT FOR INSP. 10) SUPPORT CONTROL WIRE CONDUIT AS PER CODE. |