Permit: T04CM01466

Parcel: 108163580

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/21/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/17/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) DON'T LOAD ROOF 2) NEED TRUSS DRAWINGS-LATERAL, BRACING, 3 PT BEARING 3) HANGER GIRDER TO GIRDER NOT ON PLAN, UNDER SIZED NAILS INSTALLED 4) SCISSOR TRUSS CLIPS USE 10D NOT 8D 5) INTERIOR SHEAR TRANSFERS NOT DONE 6) MISSING WIND BRACING ON EXT. WALLS ONE AT EACH END, AND AT 25' ON CENTER 7) MR. SUPERINTENDENT YOU NEED TO WALK THESE HOUSES BEFORE YOU CALL THEM IN 8) #5 SHEAR WALL NOT INSTALLED REAR "A" ?
06/15/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SHEARWALLS NOT PER PLAN (MISSED #3'S AND 5'S)