Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/24/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 08/13/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 08/06/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*PLEASE RECALL AFTER CROSS OVER. OK TO CLEAR UPGRADE. |
| 07/13/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) BONDING DEVICE NEEDED AT ALL NIPPLE POINTS AT SERVICE 250.94 2) LB COVER TO BE LOCKABLE 3) SPLIT BOLTS LISTED FOR ONLY 2 CONDUCTORS-A RUN AND A TAP 4) TIGHTEN LOOSE TERMINATIONS 5) FUSES AND REJECTION PINS ARE NEEDED |
| 05/24/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ NOTES: 1) OK TO COVER REMAINING WALLS, GROUND ALL LIGHT SWITCHES. 2) PROVIDE LETTER FROM LICENSED CONTRACTOR TO BE RESPONSIBLE FOR SYSTEM WIRING AS A SAFE AND COMPLETE SYSTEM FOR EXISTING WIRING. |