Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2004 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 09/14/2004 | MECHANICAL - HOODS | Cancelled | PER CONTRACTOR | |
| 09/10/2004 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) TIGHTEN BANDS ON FIRE WRAP. BE SURE OVERLAPS ARE MINIMUM 3". DO NOT USE SCREWS ON ACCESS DOORS ON GREASE DUCTS. FINISH WORK ON ROOF |
|
| 08/16/2004 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :*/INSPECTED GREASE DUCTS. PROVIDE A CLEANOUT AT CHANGE OF DIRECTION OK TO BUILD CHASE. BE SURE TO MAINTAIN MIN. 6" CLEARANCE INSIDE SHAFTS. |