Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM01454
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/26/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) PLEASE COMPLETE #2, 3 AND 4 OF PREVIOUS INSPECTION | |
07/22/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :SUPPORT WIRES NEEDED FOR EXIT SIGN & FLOODS SUPPORT M/C WITHIN 12" FIXTURES TO BE ATTACHED TO GRID SUPPORT WIRES TO BE ATTACHED BOTH END - 300-11 TIE WIRE NOT ALLOWED FOR FIXTURE SUPPORT |