Permit: T04CM01438

Parcel: 140213660


Addresses:

1582 E LOS CABOS PL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/14/2004 FRAMING Approved IVRS - Inspection :*
07/12/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SAME AS LAST INSPECTION
07/09/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO DWV WATER TEST 2) PLUMB OUTSIDE OF WALL CAVITY 3) NON BEARING STUD BY WATER HEATER NOTCHED MORE THAN 40 PERCENT 4) PED CANNOT BE WITHIN 6' OF WATER HEATER "B" VENT 5) NAIL PROTECT A/C COPPER 6) NAIL PROTECT ALL PLUMBING AND ELECTRIC WITHIN 1 1/4" OF WALL SURFACE 7) SEAL ALL 2ND FLOOR PENETRATIONS 8) SUPPORT DWV HORIZONTAL AT 4' ON CENTER 9) CHASE FIRE STOP REQUIRES 2 LAYERS OF 1/2" OSB 10) GAS BOND NOT THRU WALL