Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2005 | FRAMING | Approved | IVRS - Inspection :* OK TO INSULATE | |
| 07/05/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) MISSED VERT IN TRUSS FOR NAILING, VERT WALL AT GARAGE ABOVE WASHER BOX 2) NEED STUCCO, EDGE PROTECTION AT ROOF VENTS, FINISH LATH AT FRONT DOOR 3) BANG PLATE H20 LINES AT H20 HTR 4) HANGERS MISSING AT HIP JACKS TO GIRDER 5) BANG PLATES THRU-OUT 6) MOVE CLOSET LIGHT 24" AWAY FROM SHELF WALL 7) NEED BACKING FOR TUB SURROUND 8) STUDS MISSING 9) MISSING A-BOLTS THRU-OUT 10) H20 TEST POTABLE H20 11) NEED H20 IN SHOWER PAN 12) WIRE SIZE TO ATTIC HVAC, SIZE PER EQUIPMENT INSTALLED, HEAT STRIP |
|
| 07/01/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |