Permit: T04CM01395

Parcel: 140250570


Addresses:

1050 E MILTON RD 02

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/10/2005 PLUMBING - FINAL Approved IVRS - Inspection :*PLBG FINAL IS OK
OK FOR C OF O
10/06/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/30/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* LANDSCAPING BACKFLOW DEVICE REQUIRES CERTIFICATION AND SHALL BE 12" ( ABOVE MINIMUM) ALL DOWN STREAM PIPING & FLOOD LEVEL RMS.
PROVIDE LISTING FOR BRUT
PROVIDE TERMINATION OF EXTERIOR CLEANOUTS.
09/29/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO NOTICE IN ELECTRIC SERVICE PANEL
2) PROVIDE STAMPED LETTER FROM ARCHITECT ALLOWING CPVC IN LIEU OF TYPE "L" COPPER OR PEX
3) REMOVE BRANCH TAIL PIECE FROM SINK DRAIN
4) SEE NOTE #2 FROM 9/26/05
5) SCREWS EXPOSED AT SERVICE SINK SHALL BE CORROSION RESISTANT
6) RETAINING SCRW AT AVB TO BE BROKEN OFF
7) NO EXPANSION TANK AT WATER HEATER
8) BACKFLOW CERTIFICATION ?
9) INSPECTION STOPPED
09/27/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT CONNECT A CONDENSATE DRAIN TO A SINK
2) SHALL PAINT ALL VTR