Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*PLBG FINAL IS OK OK FOR C OF O |
|
| 10/06/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/30/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* LANDSCAPING BACKFLOW DEVICE REQUIRES CERTIFICATION AND SHALL BE 12" ( ABOVE MINIMUM) ALL DOWN STREAM PIPING & FLOOD LEVEL RMS. PROVIDE LISTING FOR BRUT PROVIDE TERMINATION OF EXTERIOR CLEANOUTS. |
|
| 09/29/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO NOTICE IN ELECTRIC SERVICE PANEL 2) PROVIDE STAMPED LETTER FROM ARCHITECT ALLOWING CPVC IN LIEU OF TYPE "L" COPPER OR PEX 3) REMOVE BRANCH TAIL PIECE FROM SINK DRAIN 4) SEE NOTE #2 FROM 9/26/05 5) SCREWS EXPOSED AT SERVICE SINK SHALL BE CORROSION RESISTANT 6) RETAINING SCRW AT AVB TO BE BROKEN OFF 7) NO EXPANSION TANK AT WATER HEATER 8) BACKFLOW CERTIFICATION ? 9) INSPECTION STOPPED |
|
| 09/27/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT CONNECT A CONDENSATE DRAIN TO A SINK 2) SHALL PAINT ALL VTR |