Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) DETAIL 1 PAGE A-8 HAS # 4 REBAR BENT AND RETURNED TO TIE INTO POST FTGS. DETAIL 2 PAGE A-8 HAS 1/2" REBAR GROUT SET INTO EXISTING FTG AND #4 VERTICALS 16" APART DETAIL 4) PAGE A-8 CALLS FOR APPROX 8" X 8" TOE MAINTAIN MINIMUM 3" CONCRETE ENCASEMENT REBAR |
|
| 04/22/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) REBAR NOT TO PLAN |