Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2004 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :*/ 1) OK FOR CEILING TILES 2) ON FINAL BE SURE TO PROVIDE ACCESS TO ROOF 3) SEWER VENTS MUST BE MINIMUM 10' AWAY OR 2' ABOVE OUTSIDE AIR INTAKES | |
| 06/10/2004 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/ CORRECTIONS FROM PREVIOUS INSPECTION HAVE BEEN IGNORED. |
|
| 06/08/2004 | MECHANICAL - ABOVE CEILING | Denied | PROVIDE A PLUG IN CONDENSATE CLEAN OUT FOR MIDDLE FAN COIL. PROVIDE FRESH AIR INTAKES AS PER PLANS. PROVIDE A SUPPLY DUCT TO ROOM NEXT TO LUNCH ROOM AS PER PLANS. STRAP UP FLEX DUCT OFF OF LIGHTS AND GRID. RECALL FOR INSP. |