Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM01355
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/03/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ 1) FIXTURES TO BE ATTACHED TO GRID - 410-16. IF USING MANUFACTURERS CLIPA THEY MUST BE EFFECTIVE AND LISTED. IF SCREWS WE NEED 4 AT CORNERS OR 2 ON CENTER. RESUPPORT FIXTURES RELOCATED TO NEW GRID. 2) SUPPORT FLEX CONDUIT AS PER CODE. 3) FIXTURE WHIPS MAY NOT LAY ON GRID. 4) A/C DISCONNECT NOT LISTED FOR USE IN HORIZONTAL POSITION . 5) WE HAVE CONDUCTOR OVERFILL IN BOXES. |