Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2004 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 06/03/2004 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) FIXTURES TO BE ATTACHED TO GRID - 410-16. IF USING MANUFACTURERS CLIPA THEY MUST BE EFFECTIVE AND LISTED. IF SCREWS WE NEED 4 AT CORNERS OR 2 ON CENTER. RESUPPORT FIXTURES RELOCATED TO NEW GRID. 2) SUPPORT FLEX CONDUIT AS PER CODE. 3) FIXTURE WHIPS MAY NOT LAY ON GRID. 4) A/C DISCONNECT NOT LISTED FOR USE IN HORIZONTAL POSITION . 5) WE HAVE CONDUCTOR OVERFILL IN BOXES. |