Permit: T04CM01355

Parcel: 11005014C


Addresses:

2920 N SWAN RD #207


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM01355

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/03/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ 1) FIXTURES TO BE ATTACHED TO GRID - 410-16. IF USING MANUFACTURERS CLIPA THEY MUST BE EFFECTIVE AND LISTED. IF SCREWS WE NEED 4 AT CORNERS OR 2 ON CENTER. RESUPPORT FIXTURES RELOCATED TO NEW GRID. 2) SUPPORT FLEX CONDUIT AS PER CODE. 3) FIXTURE WHIPS MAY NOT LAY ON GRID. 4) A/C DISCONNECT NOT LISTED FOR USE IN HORIZONTAL POSITION . 5) WE HAVE CONDUCTOR OVERFILL IN BOXES.