Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* APPROVED | |
| 09/15/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NOT TO BE RELEASED UNTIL FINAL 2) IF HOT WATER TO COME FROM AN INSTA-HOT STILL NEEDS IT'S OWN CIRCUIT, NOT TO BE CONNECTED TO GENERAL USE CIRCUIT VERIFY #12 WIRE TO IT OK |
|
| 09/13/2004 | ELECTRIC - INTERMEDIATE | Denied | 1) LIGHT AND SW FOR CLOSET NO IN 2) GROUND BOX FOR FRONT OUTDOOR LIGHT 3) WATER HEATER FEED AND SW NOT IN SB # 10 WIRE 4) COULD NOT LOCATE GFI RECEPTACLE FOR ROOF UNITS. DID NOT GET A REQUEST FOR 3253 | |
| 09/07/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210*/PLEASE CORRECT/ADD: 1)GROUND WIRE T OCOLD WATER PIPE. ATTACH TO PIPE WHERE IT ENTERS THE BUILDING 2)IF UNIT HAS OR WILL HAVE GAS PIPING IT TOO MUST BE GROUNDED 3)PUT PERMANENT ADDRESS LABEL ON METER SIDE OF METER BASE. USE PERMANENT METAL NO'S OR EMBOSSED METAL STRIP. "MAGIC MARKER", "SHARPIE", PEN, PENCIL, ETC. ARE NOT ACCEPTABLE |