Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/27/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) COMPLY WITH ITEM 5 OF 5/25/04 2) ALL ELSE OK TO COVER | |
| 05/25/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PEX NOT ALLOWED AS T & P LINE 2) A35 CLIPS NOT INSTALLED ON DRAG TRUSS 3) NO DWV WATER TEST 4) SUPPORT GAS LINE HING JOINT AT FURNACE 5) POST TENSION SLAB CUT TO ADD ISLAND ELECTRIC. PROVIDE ENGINEERS/CITY OF TUCSON APPROVED REPAIR |