Permit: T04CM01344

Parcel: 123120600


Addresses:

1074 E HAMPTON ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM01344

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2006 BUILDING - FINAL Approved IVRS - Inspection :*
08/24/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) PENDING CERTS
07/24/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSOR DISCONNECT NEEDS 36" CLEARANCE FROM UNIT
2) EXPOSED WIRING MECH ROOM
3) INSTALL DRIP LEGS WATER HEATER
4) SECURE GAS LINE MECH ROOM
5) SEAL MECH ROOM LID
6) INSTALL VACUUM BREAKER HOSE BIBS
7) POST ADDRESS
8) GARAGE SERVICE DOOR MUS SELF LATCH
9) GARAGE OUTLET MUST BE GFI PROTECTED
10) COMPLETE WASH BASIN LAUNDRY
11) BEDROOM 3 NORTH OUTLET TESTS ? POLARITY
12) KITCHEN CIRCUITS DO NOT TEST GFI
13) MASTER BEDROOM OUTLETS NOT ARC FAULT PROTECTED
14) BEDROOM OUTLETS 2 NOT ARC FAULT PROTECTED