Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/17/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/16/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ MC CABLE IN PATIENT CARE ROOMS MUST BE 'HFC APPROVED, GREEN COATED. THE GROUND WIRE IS IN CONTACT WITH THE METAL OF THE CABLE. THE RED INSULATED WIRE DOES NOT MEET THE REQUIREMENTS OF NEC. ART 517, 12, 13, 14, 17, 18. |