Permit: T04CM01279

Parcel: 136075290

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
05/19/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/12/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ITEMS FROM 5/7/04 INSPECTION NOT COMPLIED WITH 2, 3, 5 AND 6 NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE 2) TRUSS DRAWINGS MUST HAVE CITY OF TUCSON APPROVAL 3) PROVIDE TRUSS LAYOUT PLAN
05/07/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*/ 1) GARAGE JAMBS REQUIRE 3 KING STUDS 2) MUST PROVIDE OSHA APPROVED LADDER ACCESS TO ROOF 3) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACES 4) KING STUDS NOT CLIPPED REAR OF HOUSE 5) 15A/SD3 NOT COMPLIED WITH AT PORCH 6) P1 AT S.W. CORNER MUST EXTEND TO DOUBLE TOP PLATE 7) STUDS MUST BEAR ON PLATES. TOO SHORT 8) 10/SD4 NOT COMPLIED WITH. WEST WALL 9) STOPPED INSP. TOO MANY ITEMS