Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM01257
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2004 | FRAMING | Approved | IVRS - Inspection :* | |
06/03/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SAME AS PREVIOUS INSPECTION |
|
05/28/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) SHIM HEADER WHERE INDICATED 2) CHECK 11/SD4 AND 10/SD4 THRU-OUT 3) TRANSFER GIRDER BEAM POST TO 1ST FLOOR 4) REF OUTLET SHALL BE ISOLATED | |
05/27/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NAIL PROTECT WATER LINES AT WATER HEATER AREA 2) WATER LINE MUST BE 6" AWAY FROM B-VENT 3) NAIL PROTECT ELECTRIC WITHIN 1 1/4" FROM EDGE OF STUD 4) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC SPACE 5) NAIL PROTECT ALL PLUMBING WITHIN 1 1/2 FROM EDGE OF STUD 6) SECURE ROMEX WITHIN 8" FROM BOX 7) SHIM HEADERS 8) STOPPED INSPECTION, HAVE TRADES WALK HOUSE BEFORE RECALL |
|
05/26/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROTECT A/C LINES 2) CONDENSATE LINE MUST TERMINATE OUTSIDE OF WALL 3) PROVIDE H.35 AT STAIRS 4) PROVIDE FIRE BLOCK AT FLUE 2ND FLOOR 4) WALK YOUR HOUSE BEFORE CALLING INSPECTION |