Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ 1) OK FOR FINAL C OF O |
|
| 04/28/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) YOU CANNOT CONNECT THE PRIMARY AND SECONDARY CONDENSATE DRAINS TOGETHER. THE SECONDARY MUST DRAIN IN A CONSPICUOUS LOCATION TO ALERT THE TENANT THAT THE PRIMARY IS CLOGGED. TERMINATING 6" ABOVE LANDSCAPE AREA IS NOT CONSPICUOUS. 2) PROVIDE FUSES IN ELECT. DISCONNECT AND CONNECT LOW VOLTAGE. RECALL FOR INSP. |