Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM01199

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/ APPROVED PLANS ON SITE.
04/23/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/
04/22/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ WASTE AND VENT THRU ROOF WTR TEST OK. H2O LINE PRESSURE TEST OK. 1) WILL NEED CITY APPROVED PLAN FOR H2O AND WASTE AND VENT PER RED LINE DRAWINGS. 2) NEED LETTER FROM ENGINEER SAYING T/M IS OK IN PLACE OF T/L COPPER PIPE IN STRUCTURE.
04/21/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ WTR TEST ON WASTE AND VENT THRU ROOF AND H2O PIPING OK PENDING HAVING RED LINE DRAWING ON SITE TO COMPARE TO CITY APPROVED DRAWING OF ACTUAL INSTALLATION OF BOTH H2O SYSTEM AND WASTE AND VENT SYSTEM. 1) PROVIDE MID-STORS SUPPORT AT ALL PIPING. 2) PROVIDE APPROVED CLAMPS FOR SECURING ALL PIPING. 3) PROVIDE STAMPED LETTER FROM ENGINEER OR ARCH. GIVING OK FOR T/M COPPER IN PLACE OF T/L COPPER WHICH ALL EXISTING BLD IS.