Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 05/12/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PER APPROVED DRAWING FOOTING SHALL BE AS INDICATED ON DRAWING 24" X 12" 2) WRAP ALL PLUMBING IN CONTACT WITH CONCRETE 3) WATER TEST ON SOIL PLUMBING SHALL BE 10'-0" HIGH 4) SEWER SLOPE (VERIFY 1/4" FOOT SLOPE) 5) LEAK AT SIDE OUTLET FIXTURE 6) PVC AND AB'S SHALL NOT BE MIXED 7) SANITARY "T" NOT ALLOWED FOR 2 WAY CLEANOUT |
|
| 05/05/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SANITARY 'T' FITTING CANNOT BE INSTALLED IN THE FLAT AS DRAIN FITTINGS. USE COMBINATION T/Y FITTING OR Y FITTINGS 2) SEWER LINE MUST BE 12" BELOW GRADE OR USE DUCTIL IRON PIPE 3) YOU NEED TO INSTALL A UFER GROUND NOW 4) WRAP ALL PLUMBING THAT WILL BE IN CONTACT WITH APPROVED CLOSET WRAP. NOT PER PACK GAS WRAP 5) TOILET NOT PROPERLY VENTED. PLAN INCORRECT |