Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | ELECTRIC - TEMPORARY SERVICE | Approved | PER EL FINAL | |
| 06/24/2005 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* | |
| 06/23/2005 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ELECTRICIAN PRESENT TO OPEN EQUIPMENT. 2) BUILDING SHELL SERVICE NOT COMPLETE. NEED SHELL APPROVED BEFORE CAN RELEASE ??. 3) TIGHTEN LOCK NUTS 4) BOND JUMPERS TO BE SIZED FOR SERVICE AND 250.012 5) CORRECTLY IDENTIFY GROUNDING CONDUCTOR AT ALL OPEN AREAS. |