Permit: T04CM01191

Parcel: 110121000


Addresses:

5150 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
10/20/2005 ELECTRIC - TEMP POWER FOR TEST Approved
07/07/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :* 1) BOND ENCLOSURE 2) REJECTION PINS NEEDED AT OWNER " HP" 3) BOND JUMPER TO BE ?? PER 250. 102 7 250.66. 4) PLAN REVISION NEED 3RD PARTY STAMP.
06/24/2005 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :* 1) BOND SERVICES TOGETHER 250.58 2) PLANS NOT REFLECTIVE OF WORK INSTALLED. PLEASE REVISE PLANS OR INSTALL AS PER PLANS. WILL NEED TO BE RE STAMPED. 3) FINISH CONTACTOR.