Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM01190

Parcel: 110121000


Addresses:

5140 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
09/07/2005 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
1) OK TEMP POWER PANEL GMH-1
09/06/2005 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) MAINTAIN A SAFE APPROACH TO SERVICE EQUIPMENT 110.26
2) BRACE CABLES AS PER INSTRUCTIONS
3) FINISH LABELING OF EQUIPMENT
4) USE HARDWARE OTHER THAN DRYWALL SCREWS TO MOUNT EQUIPMENT