Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM01170
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :*/ 1) OK TO TILE | |
05/19/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) SUPPORT M/C CABLE AS PER CODE CANS. 2) WHEN ATTACHED AT CORNERS OF FIXTURE NEED 2 SCREWS. 3) FILL UNUSED OPENING IN IN BOTTOM OF PANEL. 4) PLEASE RE-INSTALL BARRIER BOARD TO SES. OK TEMP POWER FOR TEST. |