Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM01170
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PANEL OK TO COVER. 2) CONFERENCE ROOM WEST WALL. |
|
04/23/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) CAN LIGHTS M/C TO BE SUPPORTED WITHIN 12" OF BOX/FITTING 2) WE HAVE CONDUCTOR OVER FILL-CONFRENECE ROOM 3) CORRECTLY SUPPORT M/C CABLE ABOVE PANEL 4) SUPPORT PVC CONDUCTS AS PER CODE 3' + 10' 5) PLEASE PROVIDE LETTER FOR M/C CABLE AS DISCUSSED 6) OK WALLS EXCEPT AS NOTED |