Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM01155
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/29/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/24/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ MAKE CORRECTIONS. | |
06/23/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE NOTES FROM 6/21/04 INSP. 2) SECURE ALL PIPING AT APPROPRIATE INTERVALS WITH APPROVED DEVICES AND METHODS. 3) WTR TEST SHALL BE THRU ROOF ON WASTE AND VENT. 4) GAS PIPING TO BE INSTALLED PER APPROVED PLAN WITH MIN. 10 PSI ONLY 5 AT TIME OF INSP. 5) ALL GAS PIPING TO BE 6" MIN. ABOVE FINISHED GRADE. THIS IS NOT A COMPLETE LIST. HAVE YOUR PLBR PRESENT AT TIME OF NEXT INSP. |
|
06/21/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GAS PRESSURE TEST WAS AT 0 LBS - PROVIDE 10 LBS MIN. 2) CAN NOT HAVE A 2" TRAP ARM FOR LAVATORY. THIS TRAP ARM MUST BE 1½" MAX. ALL THE WAY TO THE BARREL. 3) RETEST SYSTEM LOTS OF AIR IN WTR TEST. |