Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/30/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PAINT ALL ROOF VENTS 2) GFI IN GARAGE DOES NOT TEST 3) INSTALL SUB-PANEL COVER 4) WEST EXTERIOR OUTLET NOT ? 5) INSTALL ANTI-SIPHON ALL EXTERIOR HOSE BIBS 6) HEAT PUMP EAST END OVERFUSED CALLS FOR 30 AMP MAX 7) HEAT PUMP WEST END NO FUSES 8) GAS PRESSURE TEST FINAL APPROVED |
|
| 11/10/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 1731 ADDRESS MUST BE POSTED ON HOUSE IN 3" OR LARGER NUMBERS 2) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 3) TRIM CLEANOUTS TO GRADE AND INSTALLED THREADED CAPS 4) GAS LINE MUST BE BONDED WITH #4 CONDUCTOR 5) BARE WIRES ON REAR PORCH 6) ALL OUTSIDE OUTLETS MUST BE GFCI PROTECTED 7) NON COMPATIBLE CIRCUIT BREAKERS IN EAST SUB PANEL 8) LABEL ALL CIRCUITS IN ALL SUB PANELS 9) REINSTALL MANUFACTURERS LABEL IN EAST SUB PANEL 10) A/C CONDENSATE |