Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES OR FLUSH IN COMBUSTIBLES. NEED AN APPROVED EXTENDER RING. METAL NOT APPROVED 314.20 2) OPEN SPLICES AT FIXTURE NOT ALLOWED 3) FIXTURES TO BE LISTED AND LABELED 4) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 5) SUPPORT PHOTO CELL CONDUIT 6) CORRECTLY INSTALL SEAL TITE FITTINGS AND TIGHTEN 7) MISSING A/C DISCONNECT BOND SCREW 8) LABEL ROOF UNITS |