Permit: T04CM01124

Parcel: 140323580

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM01124

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2004 FRAMING Approved IVRS - Inspection :*
04/28/2004 FRAMING Partial Approval IVRS - Inspection :*
04/26/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BLOCK ALL MECHANICAL 2) NAIL PROTECT ABS AT MASTER W.C. 3) NAIL PROTECT WATER LINE AT MASTER BEDROOM 4) GAS TEST AT 3 PSI, 10 PSI MINIMUM REQUIRED 5) FIRE BLOCKS MISSING AT MASTER BATH 6) NAIL PROTECT ROMEX AT LIVING ROOM 7) NAIL PROTECT DRYER VENT 8) MOVE DUCT AWAY FROM GUSSETT PLATE AT HALL 9) W.C. IN HALL BATH FLANGE LESS THAN 15" ON CENTER