Permit: T04CM01120

Parcel: 127080830


Addresses:

5409 E 7TH ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/24/2004 BUILDING - FINAL Approved IVRS - Inspection :*
08/17/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) RAISE DISHWASHER DRAIN LINE TO COUNTER BOTTOM 2) GFI'S NOT WORKING-HALL BATH, NORTH EXTERIOR OF MAIN HOUSE, WEST EXTERIOR OF GUEST HOUSE (BREAKER TURNED OFF BY INSPECTOR) 3) SEAL TOILETS TO FLLOR 4) CANNOT USE POINTED SCREWS IN GUEST ELECTRIC PANEL 5) GUEST PANEL NEEDS IT'S OWN GROUND RIDS AND MAIN PANEL 6) FURNACE 'B' VENT NEEDS 1" CLEARACNE TO COMBUSTIBLES AT ATTIC FLOOR AND ROOF (PROVIDE LADDER FOR ATTCI ACCESS FOR INSPECTION 7) PAINT PVC CONDENSATE ON EXTERIOR