Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/25/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) "B" TRUSSES NOT BEARING ON BEARING WALL. 4 TRUSS BRACES MISSING. ALSO "C" TRUSSES 2) T & P HAS REVERSE FLOW AND NOT RATED FOR 210. 3) REVISE ELECTRIC PLAN TO AS BUILT 4) 5/SD3 NOT COMPLIED WITH. SHEAR NOT NAILED TO ROOF 5) NAIL GARAGE SHEAR PER SCHEDULE. BLOCK ALL EDGES 6) SHEAR PANEL DAMAGED ABOVE BATHROOM. PEX CANNOT PENETRATE 7) 2- 2 X 4'S REQUIRED UNDER ARCH HEADER 8) SUPPORT/BLOCK GAS HINGE JOINT AT FURNACE |
|
| 05/21/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) NEED TRUSS DRAWINGS TO DETERMINE INTERIOR BEARING PTS 2) DON'T USE PEX WIRBO FOR T & P 3) T-FOR GAS LINE IN LAUNDRY, WITH STUB OUT AND CAP REQUIRES A GAS VALVE AND ACCESS 4) AT FRONT DOOR SIX SWITCHES, PLAN SHOWS 3 ? 5) DON'T LOAD ROOF UNTIL BEARING PTS VERIFIED AND SHIMED 6) FINISH STUCCO LATH |