Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/28/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NAIL PROTECT ELECTRIC IN KITCHEN |
|
| 05/26/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 2) NAIL PROTECT ELECTRIC AT KITCHEN AND BEDROOM 3 3) FIRE STOP MECH CAHSE 2ND FLOOR DEN INTO ATTIC 4) NAIL PROTECT CONDENSATE LINE 2ND FLOOR 5) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT B-VENTS |
|
| 05/25/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ITEMS NOT CORRECTED |
|
| 05/24/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) A.35'S GARAGE FRONT WALL 2) 1" CLEARANCE TO B VENTS 3) STUD SPAN UNDER WINDOWS 4) NAIL PLATE BEDROOM 3 AND KITCHEN 5) DRAIN REVERSE SLOPE 6) NO WATER TEST 7) SUPPORT ALL DRAINS 8) NAIL STRAP TP LINE 9) FLAPPER ON WEST WALL VENT 10) FIRE BLOCK ON DUCT SE CORNER 11) NAIL STRAPS ON CONDENSATE LINE |