Permit: T04CM01065

Parcel: 116120700

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/27/2005 BUILDING - FINAL Approved IVRS - Inspection :*
06/22/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SAME AS INSPECTION OF 7/21/04
07/21/2004 BUILDING - FINAL Denied IVRS - Inspection :INSTALL FULL SIZE WATER HEATER P&R LINE TO EXTERIOR OF CABINET
UNCOVER TO VERIFY ALL ELECTRIC GROUNDS AND BONDS
UNCOVER UNDERGROUND ELEC CONDUIT AND SUB PANEL
INSTALL SMOKE DETECTORS PER PLAN
APPEARS UNIT #2 125 AMP DISCONNECT UNDER SIZED
07/19/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
07/14/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) APPEARS ELECTRIC PANEL UNIT #2 125 AMP MAIN IS OVERLOADED WITH 100 MAIN TO UNIT #1
06/14/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY PER OWNER REPRESENTATIVE
06/10/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ELECTRIC NOT PER APPROVED PLAN 2) CEILING FAN TO LOW 3) GFCI INOPERABLE 4) SEAL AROUND SHOWER AND TOILET BASE 5) INSTALL SMOKE DETECTOR LEADING TO BEDROOMS 6) INSTALL WATER HEATER PTR LINE TO EXTERIOR OF CABINET 7) PAINT EXPOSED VTR'S 8) CHECK ELECTRIC CALC'S, GROUNDING, BOND, ETC... 9) STOPPED INSPECTION 10) SEE WRITE UP ON #1
03/25/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*