Permit: T04CM01049

Parcel: 13355231A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM01049

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) 4-IN HOUSE BACKFLOW CERTIFICATIONS 2) 1-EXTERIOR BACKFLOW CERTIFICATIONS
07/07/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) DRAINS FROM RP'S TO BE SEPERATE PER REQUIREMENTS FOR INDIRECT DRAINAGE 2) H2O SUPPLYS TO BACKFLOW PREVENTION DEVICES TO BE FULL SIZE PIPING PER 610.2 94 UPC 3) INTERMINGLING OF BRASS AND GALVENIZED PIPING DOES NOT ELIMINATE CORRISION PIPE THESE DEVICES WITH COPPER OR PROVIDE DIELECTRIC PROTECTION 4) PROVIDE APPROVED CLAMPS ON COKE MACHINE DRAINS
07/02/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) MAKE CORRECTIONS NOTED ON 7/1/04 2) 10 PSI AIR TEST ON GAS PIPING FOR ? OK 3) GAS CARD AT METER
07/01/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) INDIRECT DRAINS SHALL HAVE MIN. 1" AIR GAP AT FLOOR SINKS AND BE RIDGID PIPING FULL SIZE. 2) ALL INDIRECT DRAINS TO BE SEPERATE AND IF OVER 5' IN LENGTH TRAPPED AT APPLIANCE. 3) SEPARATE BACKFLOW PROTECTION IS REQUIRED FOR EACH CARBONATOR AND H20 SUPPLY TO EACH FOUNTAIN MACHINE FOR WTR MIXED WITH ANY OTHER SUBSTANCE. 4) MIN. 10 PSI TEST ON GAS IN PLACE AT TIME OF INSP BECAUSE OF CHANGES TO SYSTEM. 5) CORRECT DRAINAGE AT 3 COMP SINK IN REAR OF BLD.