Permit: T04CM01035

Parcel: 123030610


Addresses:

1521 N BENTLEY AV

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/07/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/31/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PATIO DOOR CALLS FOR 2 X 10 HEADER 2 X 8 INSTALLED 2) 60 WINDOW AND 80 WINDOW PLAN SHOWS 2 X 8 HEADERS HAVE SPAN RECALUCULATED FOR HEADER SIZES 3) LEDGER ENDS MUST LAND ON STRUCTURAL MEMBER AT SPLICES 4) 10/7 A35 CLIP MUST EXTEND THRU OSB TO LEDTGER OR USE H2.4 CLIPS ALSO 5) OSB ROOF PANELS MUST BE NAILED AT 6" ON ALL ENDS AND SUPPORTED EDGES AND 12" IN FIELD 6) OSB ROOF PANELS MUST BE INSTALLED WITH GRAIN PERPENDICTULAR TO RAFTERS OR BLOCK ALL EDGES AND 24" ON CENTER IN FIELD 7) EXPOSE ALL LEDGER CLIPS 8) PROVIDE PROOF OF CABIN TIES AT CORNERS 9) BLOCK ALL DROP CEILINGS 10) STUCCO WEEP SCREED MUST BE 4" ABOVE SOIL 11) INTERMEDIATES NOT INSPECTED