Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/07/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/ OK TO COVER ALL AREAS.
06/04/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) A TRAP ARM MAY NOT CHANGE SIZE. 2) THE TRAP IS TO BE THE SAME SIZE AS THE TRAP ARM. 3) THR TRAP MAY ONLY BE ONE SIZE LARGER THAN THE TAILPIECE. 4) A TRAP ARM MAY NOT EXCEED THE DISTANCE ALLOWED IN TABLE 7-1 BUT IN NO CASE BE SHORTER THAN 2X THE PIPE DIAMETER. 5) OK TO COVER EXCEPT LAUNDRY ROOM.
06/01/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) PROVIDE TEST ON ALL PIPING. 2) GAS PIPING WILL REQUIRE CITY APPROVED PLAN ISOMETRIC OF ACTUAL GAS INSTALLATION.
04/06/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ ABS UNDERGROUND OK. OK TO COVER.