Permit: T04CM01020

Parcel: 141304520

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM01020

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2004 BUILDING - FINAL Approved IVRS - Inspection :*
05/19/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) IN SERVICE PANEL (2) CIRCUITS MARKED SALES OFFICE ? 2) 20 AMP BREAKER PROTECTING A #14 CU WIRE 3) #10 CU. FED BY A 20 AMP BREAKER, BLACK WIRE ON THE NEUTRAL BAR 4) BLANK OFF OUTLET UNDER KITCHEN COUNTER OVER HANG 5) WATER HEATER NOT CONNECTED TO FLUE