Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM01020
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
05/19/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) IN SERVICE PANEL (2) CIRCUITS MARKED SALES OFFICE ? 2) 20 AMP BREAKER PROTECTING A #14 CU WIRE 3) #10 CU. FED BY A 20 AMP BREAKER, BLACK WIRE ON THE NEUTRAL BAR 4) BLANK OFF OUTLET UNDER KITCHEN COUNTER OVER HANG 5) WATER HEATER NOT CONNECTED TO FLUE |