Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FILL IN OPEN CABLE TRENCH. ELECTRIC FEEDER CABLES MUST BE UNDER 24" OF SOIL 2) MAX ALLOWED CIRCUIT BREAKER ON A/C 40 AMP 50 INSTALLED 3) CONDENSATE MUST HAVE 1" AIR GAP ALSO SOFT WATER DRAIN 4) PROVIDE CITY APPROVED REVISED ELECTRIC PLAN FOR ADDED 220 VOLT 50 AMP CIRCUIT IN GARAGE. WELDER CIRCUITS NOT ALLOWED 5) ELECTRIC OUTLET REQUIRED WITHIN 6 FEET OF KITCHEN ACCESS ON DIVIDER WALL BEHIND KITCHEN SINK. SEE PLAN 6) BACK PORCH HAS BEEN ADDED WITHOUT PERMIT HAVE SITE PLAN REVISED AND PROVIDE PROOF OF PERMIT FEES PAID 7) STOPPED INSPECTION. TOO MANY ITEMS |