Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* ALL ITEMS PER PAST INSPECTION ON 5/3/06 CORRECTED |
|
| 05/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTES: 1. SUPPORT CONDUIT ABOVE CEILING PER CODE. 2. J-BOX WILL HAVE TO BE ACCESSIBLE. 3. MORE THAN 3 CURRENT CARRING CONDUCTORS IN HOMERUN CONDUIT, DE RATE ACCORDINGLY. 4. WHERE IS NEW PANEL "P" 5. PLASTIC PANCAKE BOX NOT FAN RATED? VERIFY, ALSO VERIFY LISTING FOR 1/2" KO. MC TERMINATION. |
|
| 05/01/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE LAST INSPECTION WAS DENIED 4/28/06 CANNOT LOCATE LAST INSPECTORS COMMENTS, RECALL INSPECTION - LEAVE MSG, OR MEET INSPECTOR ON SITE. |
|
| 04/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED A PLAN TO REVIEW. PLEASE RECALL AND HAVE ON SITE. |