Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :*/ 1) REINSPECT | |
| 11/12/2004 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) DRYER CIRCUIT REQUIRES 3 INSULATED WIRES, PLUS GRD. USE CORRECT COLOR FOR WIRE USE, AT MAIN SERVICE 2) SUB PANEL FEED 100 AMP, PULLING TO MUCH POWER OUT OF SUB-PANEL "B", (2) 100 2 POLE, (2) 60 AMP 2 POLE, (1) 30 2 POLE AND (1) 20 SINGLE POLE 3) PUT 100 SUB-FEED INTO HOUSE IN CONDUIT, PLASTIC SCHEDULE ? 4) CHANGE WASHER BREAKER TO 20 AMP 5) RE-DISTRIBUTE LOAD, RE-CALCULATE |
|
| 11/02/2004 | BUILDING - FINAL | Denied | HAD BEEN APPROVED IN ERROR BY A. MATHIESON ON 7/7/04 |