Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM00986
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2004 | PLUMBING - INTERMEDIATE | Approved | ||
04/07/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WTR TEST ON INDIRECT WASTE SYSTEM SHOWN ON APPROVED PLAN THRU ROOF. H2O PIPING IN WALL 100 PSI AIR TEST OK. 1) THIS INDIRECT WASTE SYSTEM DOES NOT MEET MIN. REQUIREMENT OF STATE CODE AND WILL REQUIRE DIRECTION FROM STEVE LONG OR CODE ADMINISTRATOR. WASTE AND VENT IN LOUNGE AREA APPROVED FOR SINK AND FLOOR SINK. 2) H2O FOR WTR HTR AND SERVICE WILL NEED TO BE INSPECTED. | |
03/30/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ H20 PIPING IN WALL ONLY STUBBED OUT ABOVE FLOOR SINK - PARTIAL APPROVAL. 100 PSI AIR TEST. 1) SEE SECTION 413.3 FOR FOOT SPA DRAINAGE, PLAN POSSIBLY APPROVED IN ERROR. SEE ALSO 801.3 AND 801.0. 2) C.O. AT END OF INDIRECT WASTE PIPING TO BE LONG RADIUS DRAINAGE FITTING AT 90o. 3) WTR TEST SHALL BE THRU ROOF ON ALL VENT PIPING. 4) INDIRECT WASTE PIPING SHALL BE RUN SEPERATLY FOR EACH FIXTURE. LOUNGE 101 WTR TEST ON WASTE PIPING FOR SINK IS OK. |