Permit: T04CM00977

Parcel: 116120700

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/23/2005 BUILDING - FINAL Approved IVRS - Inspection :*
06/22/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SAME AS INSPECTION OF 7/21/04
07/21/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/19/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
06/14/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) NOT READY PER OWNER REPRESENTATIVE
06/10/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BREAKERS USED IN SUB-PANEL OTHER THAN THOSE SPECIFIED BY LISTING 2) INSTALL RANGE HOOD 3) KITCHEN ELECTRIC OUTLETS NOT PER PLAN 4) BASEBOARD HEATERS CANNOT BE INSTALLED UNDER ELECTRIC OUTLETS 5) GFCI'S NOT WORKING 6) SEAL AROUND BASE OF TOILET AND TUB 7) INSTALL ALL LIGHTS, SWITCHES, OUTLETS, ETC... 8) APPEARS ALL BASEBOARD HEATERS ARE NOT ADDED TO ELECTRIC CALC'S 9) NEED VERIFICATION OF ELECTRIC PANEL GROUNDING 10) INSTALL SMOKE DETECTORS IN HALLS LEADING TO BEDROOMS 11) POST ADDRESS NUMBERS ON UNITS VISIABLE FROM STREET 12) INSTALL ANTI-SIPHON HOSE BIBS 13) SEAL AROUND EVAP COOLER PENETRATION INTO UNIT 14) INSTALL FUSED DISCONNECT EVAP COOLER 15) PERMANENTLY LABEL ALL CIRCUITS SERVED IN PANEL BOXES (ELECTRIC) 16) PAINT EXPOSED PLUMBING VENTS ON ROOF 17) INSTALL NO-LOX ALUMINIUM CONDUCTORS 18) ELIMINATE ALL WIRING UNUSED IN PANEL BOXES 19) NEED VERIFICATION OF ELECTRIC CONDUIT UNDERGROUND 20) RENTAL UNITS NEED VERIFICATION OF LICENSED/SUB-CONTRACTOR 21) STOPPED INSPECTION
03/25/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*