Permit: T04CM00964

Parcel: 13419042C


Addresses:

7160 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Permit Number - T04CM00964

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2004 MECHANICAL - PROGRESS Approved
07/06/2004 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*/ 1) DUCTS (RETURN AIR) ABOVE CEILING GRID. OK . LOCATION IN REAR OFFICES OF BLDG. THIS WORK SHOULD 04036 ABOVE CEILING
06/25/2004 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*/ COMBUSTABLES NOT ALLOWED IN A RETURN AIR PLENIUM. SUPPORT FLEX DUCTS MAX 5' SPACING. SUPPORT RETURN AIR BOOTS. FIRE DAMPER OPENING TOO BIG AT BREAK ROOM. INSPECTED CONDENSATE DRAIN LINES. HAVE PLANS REVISED IF DUCTING THE RETURN AIR. INSPECTED SPACE HEATERS. OK FOR CEILING TILES IN GOLF AREA,
06/17/2004 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*/ INSPECTED FIRE DAMPER OPENINGS. OK TO INSTALL DAMPERS.