Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T04CM00964
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
| 07/06/2004 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 75 KVA TRANS NOT GROUNDED NUETRAL TO UFER 2) SWITCH PARALLELL CONDUCTOR TO SAME BREAKER 3) SW OUT CHASE NIPPLE TO 480V PANEL AT SIDE LB. 4) TWO CIRCUIT BREAKERS-175A CLIP AND 225A CLIP IN DIFFERENT AREAS 5) ISLOATION GROUND IN WRONG PLACE |
|
| 07/02/2004 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 06/30/2004 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* |