Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 11/02/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK LAST 35' TO SERVICE-4" PVC |
| 09/07/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK WALLS SUBJECT TO M/C LETTER |
| 09/01/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) PROTECT PVC STUBS AT WALLS 2) FINISH EXHAUST FANS 3) SUPPORT M/C WITHIN 12" OF BOXES 4) SUPPORT CONDUIT CLOSER TO PVC TRANSITION 5) PLEASE PROVIDE LETTER AUTHORIZING USE OF M/C CABLE |
| 07/08/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :*/ 1) OK OUTSIDE CANS AND LIGHTS 2) PLEASE CHECK ON EM LIGHTS AT EXITS AND PROVIDE A LETTER FOR DELETED LIGHTS AND SIGN ? |